Previous Page      Next Page      Section-01   Page-28

BIOBOR® JF ADDITIONS FOR LARGE JET FUEL TANKS

 USAGE SCHEDULE

JET FUEL

SHOCK TREATMENT@270PPM

MAINTENANCE LEVEL @135 PPM

GAL.

LBS.

GAL.

Fl. OZ.

GAL.

LBS.

100 670 0.02 2.63 0.01 1.32
200 1340 0.04 5.26 0.02 2.63
300 2010 0.06 7.89 0.03 3.95
400 2680 0.08 10.53 0.04 5.26
500 3350 0.10 15.16 0.05 6.58
1,000 67000 0.21 26.46 0.10 13.16
2,000 13400 0.41 52.92 0.21 26.46
2,500 16700 0.52 66.80 0.26 33.04
5,000 33500 1.03 132.16 0.52 66.06
10,000 67000 2.07 264.47 1.03 132.31
20,000 134000 4.14 528.94 2.05 264.62
50,000 335000 10.35 1,322.35 5.15 661.55

To determine the fluid ounces of BIOBOR® JF required to give a concentration of 270 PPM, multiply pounds of fuel by 0.004 and for 135 PPM, by 0.002.  Density of Jet Fuel: 1 gallon weights 6.714 pounds


BIOBOR® JF METRIC CONVERSIONS FOR VARIOUS FUELS
“SHOCK TREATMENT AT 270 PPM
  Fuel Density At
15o C / 59o F

Oz of BIOBOR ® JF
per 100

ml of BIOBOR ® JF
per1000

FUEL

G/ml

lbs/gal

kg/L

Gal. Fuel

LBS.

JP-4 0.7601 6.343 3.694 25.37 198.27
Kerosene (Turbine Fuel) 0.8045 6.714 3.910 26.86 209.57
Diesel # 1 0.8180 6.827 4.002 27.31 214.50
Diesel # 2 0.8484 7.080 4.123 28.32 220.99
Buncker “C” 0.9952 8.305 4.737 33.22 259.26

To determine the fluid ounces of BIOBOR® JF required to give a concentration of 270 PPM, multiply pounds of fuel by 0.004 and for 135 PPM, by 0.002.


To determine the milliliters of BIOBOR® JF required to give a concentration of 270 PPM, multiply kilograms of fuel by .0536 and for 135 PPM, by .0268.


BIOBOR ® JF is manufactured and sold for prevention and elimination of microbial growth in all hydrocarbon fuels such as aviation jet fuel, kerosene, no 1 and no. 2 diesel fuels, home heating oil, marine diesel and bunker “C” fuel.

STOP FUNGAL GROWTH IN FUEL

Several forms of fungi can survive and multiply in hydrocarbon fuels. These fungi grow into long strings, and form large mats of globules. The growth appears slimy and is usually black, brown or green. It may grow throughout the fuel or at the interface between the fuel and water bottom layer. As fuel is agitated during filling, fungal growth is distributed throughout the fuel system where it will cling to walls and supporting structures within the fuel tank. This fungal growth can do serious damage to instrument probes, filters, fuel lines, seals and even the fuel tank and engine.

Biobor® JF is a biocide used to inhibit fungal growth in fuels. It is used to kill the existing growth in contaminated tanks and is a preventative measure in clean tanks. It is recognized and recommended by leading engine and equipment manufacturers throughout the world as an effective means of inhibiting the growth of Cladosporium resina and Pseudomonas Aerogenous organisms in fuel.

16 FL. OZ. “EASY SQUEEZE”

Biobor® JF in the new 16 oz. “Easy Squeeze” container is specifically packaged for the customer that wishes to treat their fuel in the proper manner (1 oz. / 40 gal.-shock, 1 oz. / 75 gal.-maintenance). This “Easy Squeeze” package provides the consumer the opportunity to semi-blend the Biobor® JF into the fuel as the tank is filled.

BIOBOR® JF SHOWN IN THE NEW “EASY SQUEEZE” CONTAINER

EPA REG. NO. 65217-1
EST 61879-TX-0001

THE EASY WAY TO DO A DIFFICULT JOB!

This type of dispenser:
1. Makes measurement of Biobor ® JF precise.
2. Blends Biobor® JF into fueling stream easily as tank is being filled.
3. Requires on additional measurement devices or add rations
calculations.
4. No spill miss because all Biobor® JF goes directly from the “Easy
Squeeze” container into the fuel.

DIRECTIONS
This container is designed so the product may be added in exact measured quantities during the fueling operation. After the tank is approximately 1/2 full, begin adding the product from the measured control area of the container into the tank to the desired dosage. Never add to an empty tank. (1) Make sure black cap is on tightly (main bottle) (2) Loosen white cap covering measured control area. (3) Squeeze sides of container lightly in order to fill measure control area into fuel tank. (4) Remove white cap and pour product from measured control area into fuel tank. (5) Replace white cap and repeat steps #3 and #4 as required to treat the desired furl quantity. (6) After required treatment is completed, make sure all caps are on tightly in order to eliminate moisture contamination of the product.

BULK PACKAGE
Biobor® JF is also available in large size. Bulk users may obtain Biobor® JF in quart cans, 40lb drums (5-Gallons). The bulk user should investigate using a Hammonds Additive Injector in conjunction with their additive. These injection units are ideal for blending Biobor® JF into fuels at higher flow rates.

HUM-BUG DETECTION® KIT
Any Biobor® JF program should be monitored by the HUM-Bug Detector® Kits. This kit will confirm Biobor® JF treatment effectiveness

Previous Page      Next Page      Section-01   Page-28